Muhammad, Mustangin, ST M.Eng (2021) ANALISIS PERHITUNGAN PENDINGINAN TRAFO MENGGUNAKAN ISOLATOR CAIR MINYAK SAWIT (Jurnal & Peer Review). Jurnal Agro Fabrica, 3 (2). pp. 40-51. ISSN ISSN : 2656-4831 (Cetak) ISSN : 2656-4823 (Online)
jurnal MST oil trafo CPO.pdf - Published Version
Download (852kB)
PEER REVIEW Oil Trafo CPO.pdf - Published Version
Download (1MB)
jurnal_MST_oil_trafo_CPO_Cek Similarity.pdf - Published Version
Download (2MB)
Abstract
The transformer that functions to increase/decrease the voltage is heated due to the flow of electric current.
The heat must be removed so as not to damage the winding. The heat dissipation method uses a liquid to
propagate heat into the air. Currently, mineral oil is generally used, but to improve the environment and be
more sustainable, it can be replaced with palm oil (CPO). The heat transfer palm oil of the transformer can
be calculated. The heat propagates from the heat source through the paper to the CPO, then to the iron
casing of the transformer and then to the free air. In order for CPO to cool properly, CPO needs to be cooled
using forced air so that the heat transfer process is optimal. Based on the assumption of transformer
parameters and CPO parameters such as heat capacity, conductivity, density, viscosity and others, it is
obtained that the flow properties of CPO are laminar with Reynolds number of 293. Pradle number of 173.99
and Prandtl number of 30, then the convection coefficient CPO heat is 509.4 W/m2.oC. Based on the
temperature in the coil of 80oC, the temperature calculation on the coil wrapping paper is 72oC, the
temperature on the inside wall of the casing is 54.17oC and the temperature on the outer wall of the
transformer or in the free air is 53.53oC so that it is still below the standard or acceptable. This shows that a
5,000 Watt heat source with a transformer casing length and width of 0.5 meters and a total radiator pipe
length of 10 meters can reduce heat in the transformer. The comparison of the outside temperature in the air
compared to the standard is 53.5oC/60oC or 89.2%.
Item Type: | Article |
---|---|
Creators: | Creators NIM/NIDN Muhammad, Mustangin, ST M.Eng 0522117601 |
Uncontrolled Keywords: | heat convection, Palm oil, Transformer cooling, heat transfer |
Subjects: | 600 – Teknologi (Ilmu Terapan) > 620 Ilmu teknik dan ilmu yang berkaitan > 620 Ilmu teknik dan ilmu yang berkaitan |
Divisions: | DIII Teknik Mesin |
Depositing User: | Admin Perpustakaan |
Date Deposited: | 04 Feb 2022 07:02 |
Last Modified: | 07 Feb 2022 03:27 |
URI: | https://repository.polteklpp.ac.id/id/eprint/1347 |